SYNOPSIS:
ELECTRICAL
ENERGY COST IS RISING EVERY YEAR. Don't throw valuable money down
the drain by wasting Electrical Energy, which is in short supply,
when there are simple , easy and economical ways of saving this
precious commodity, using cost effective retrofit devices. This
will also enable you to reduce costs and become more competitive,
LOCALLY AND GLOBALLY.
TEXTILE
MOTOR ENERGY SAVER FOR USE WITH RING FRAME/TWO FOR ONE TWISTERS,
CARDING MACHINES, BLOWERS, ETC., TO SAVE ENERGY, IS A SHORT PAY
BACK LOW COST ENERGY SAVING RELIABLE PRODUCT WHICH CAN BRING IN
IMMEDIATE BENEFITS. THIS IS TO BE INTERFACED WITH THE STAR DELTA
STARTER. WHENEVER LOAD IS LOW, THE MOTOR OPERATES IN STAR MODE
TO SAVE ENERGY. |
MODEL
TMES |
TOP
ADVANTAGES
ENERGY
SAVING CASE STUDIES :
CASE
STUDY NO.1 :
Textile
Motor Energy Saver interfaced with STAR DELTA STARTER of the Ring Frame.
| MOTOR
CAPACITY |
: |
40
KW |
| FULL
LOAD CURRENT |
: |
68
amp. |
Energy Measurements were made using a Power Analyser on pershift basis
:
| Savings
Observed |
: |
5
units/shift of 8 hours |
| Number
of Shifts/day |
: |
3 |
| Number
of working days in a year |
: |
350
days |
| Total
Energy Saving/year |
: |
5250
units |
| Savings/Year
in Rupees @ Rs.5.00 per unit |
: |
Rs.
26,250/- |
Savings/Benefit
due to reduction in Maximum Demand and improvement in Power Factor
has not been taken into account.
CASE
STUDY NO.2 :
Textile
Motor Energy Saver interfaced with STAR DELTA STARTER of the Ring Frame.
| MOTOR
CAPACITY |
: |
34
KW |
| FULL
LOAD CURRENT |
: |
60
amp. |
SAVINGS
:
a)
Energy Consumed per Doff of 3.5 hrs. :
| Without
Textile Motor Energy Saver |
: |
77.3
  units |
| With
Textile Motor Energy Saver |
: |
76.8
  units |
| Energy
Saving per day |
: |
  3.12 units |
b)
Savings due to reduction in Maximum Demand :
| KVA
without unit |
: |
3
* 400 Volts * 31.5 Amps |
: |
21.82
KVA |
|
KVA with unit |
: |
3
* 400 Volts * 20.7 Amps |
: |
14.34
KVA |
| Reduction
in Maximum Demand |
: |
  7.48 KVA |
| Average
Reduction in M.D. |
: |
 
1.87 KVA per month |
| Savings
per year @ Rs. 150/- per KVA |
: |
Rs.
3366/- |
| |
| Total
Savings per Year |
: |
Rs.
8826/- |
CASE STUDY NO.3 :
Textile
Motor Energy Saver interfaced with STAR DELTA STARTER of the Ring Frame.
| MOTOR
CAPACITY |
: |
34
KW |
| FULL
LOAD CURRENT |
: |
60
amp. |
SAVINGS
:
a)
Doff Period 3 hrs. :
| Savings/doff
of 3 hrs. |
: |
1.2
units |
| Savings/day |
: |
9.6
units |
| Savings/year |
: |
3360
units |
| Cost
Savings/year |
: |
Rs.
16800/- |
b) Savings due to reduction in Maximum Demand :
|
KVA without unit |
: |
3
* 325 Volts * 39 Amps |
: |
26.68
KVA |
| KVA
with unit |
: |
3
* 395 Volts * 34 Amps |
: |
23.26
KVA |
| Reduction
in Maximum Demand |
: |
 
3.42 KVA |
| Total
doff period |
: |
3
hrs. |
| Average
Reduction in M.D. |
: |
1.14
KVA per month |
| Savings
/ year @ Rs. 150/- per KVA |
: |
Rs.
  2052/- |
| |
| Total
Savings per year |
: |
Rs.
18852/- |
Benefit
due to Power factor improvement, (0.76 to 0.89) has not been taken into
account.